Contact Us

Support EATON UPS System Eaton Make 10 KVA On-Line UPS With Internal Batteries

Eaton Make 10 KVA On-Line UPS With Internal Batteries

UPS System On Line UPS

0.00

Model 9145 10Kin

Reset default

Specification

Output Specification
Output Capacity (KVA )
10 KVA
Output Capacity (KW )
9 Kw
Output Power Factor
0.9 Power Factor
Output Phase
1 Phase
Other Output Phase
Output Voltage
230 Volt
Other Output Voltage
208 Or 240 Volt
Efficiency at Full Load
>94 %
Output Voltage Distortion
<1 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Output Frequency (not synced)
60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
Load Crest Factor
3:1
Output Voltage THD
<2 %
Transfer Time
<0 Ms
Output Waveform type
Sine Wave
Output Connections
Hard Wire 3 wire (1PH+N+G)
Bypass
Internal Bypass (automatic & manual)
UPS Parallel Upto
Overload Capacity
Optional
Input Specification
Input Voltage
230 Volt
Other Input Voltage
208 Or 240 Volt
Input Phase
1 Phase
Other Input Phase
Input frequency
50/60Hz +/- 3 Hz
Input Voltage Range (Output Derated)
110 - 276 Volt
Input voltage range for main operations
160 - 276 Volt
Input frequency Range
45 - 55 Hz
Input Power Factor
>0.99 None
Input Connections
Hard Wire 3 wire (1PH+N+G)
Input Protection
Batteries & Runtime
Battery DC Bus
Maximum Charger Capacity
4 Amp.
Battery Position Option
Internal
Battery Type Compatibility
SMF Battery
Batteries Recharge Time upto 90%
<5 Hrs.
Approved Battery Capacity (AH)
Communication & Management
Control panel
Multi-function LCD status and control console
SNMP Management
Optional
Power Management Software
In-Built
Interface Port(s)
DB-9 RS-232, Smart-Slot
Audible Alarm
Audible and visible alarms prioritized by severity
Audible noise at 1 meter from surface of unit
<55 Decibal
Physical
Maximum Height
708 Mm
Maximum Width
260 Mm
Maximum Depth
550 Mm
Shipping Height
Shipping Width
Shipping Depth
Net Weight
84 Kg
Shipping weight
Rack Height(U)
Colour
Environmental
Operating Temperature
0 - 40 °C
Operating Relative Humidity
0 - 95 % Rh
Operating Elevation
Storage Temperature
-20 - +60 °C
Storage Relative Humidity
Storage Elevation
Compliances
Compliance
IS 16242 (Part1): 2014
Approvals
IS 16242 (Part1): 2014
Other Environmental Compliance
IS 16242 (Part1): 2014
Other Specifications
Technology
Double Conversion Online
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Surge Protection
Yes

Services