Specification
Output Capacity (KVA )
80 KVA
Output Capacity (KW )
80 KW
Output Power Factor
1 Power Factor
Other Output Voltage
380 Or 415 Volt
Efficiency at Full Load
> 95 %
Output Voltage Distortion
< 3 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Output Frequency (not synced)
+/- 0.1% for 50/60Hz Nominal
Output Voltage THD
< 3% linear load and <5% non-linear load
Output Waveform type
Sine Wave
Output Connections
Hard Wire 5-wire (3PH + N + G)
Bypass
Built-in Maintenance Bypass
Overload Capacity
150% for 1 minute 125% for 10 minutes
Other Input Voltage
380 Or 415 Volt
Input frequency
50 Or 60 Hz
Input frequency Range
45 - 65 Hz
Input Voltage Range (Output Derated)
277 - 485 Volt
Input voltage range for main operations
304 - 477 Volt
Input Connections
Hard Wire 5-wire (3PH + N + G)
Battery DC Bus
384 - 552 VDC
Battery Type Compatibility
SMF / Flooded Batteries
Battery Position Option
External
Approved Battery Capacity (AH)
65 - 200 Amp.
Battery Circuit Breaker
Optional
Communication & Management
Power Management Software
Optional
Audible Alarm
Audible and visible alarms prioritized by severity
Audible noise at 1 meter from surface of unit
< 60 Decibal
Operating Relative Humidity
0 - 95 %
Operating Temperature
0 - 40 °C
Technology
Double Conversion Online