Contact Us

Brand NUMERIC UPS System On Line UPS Numeric Make 10 KVA 3:1 Phase On-Line UPS ( HP Max Series )

Numeric Make 10 KVA 3:1 Phase On-Line UPS ( HP Max Series )

UPS System On Line UPS

Price: 153400

You save 76700

HP Max is a Single Phase Double Conversion OnLine uninterruptible power supply with high frequency PWM technology. It offers unparalleled 0.9 power factor, enabling support for demanding IT and critical loads across segments.  With upto 94% efficiency, it helps reduce operating cost. HP Max is solar compatible.

Segments
IT & ITes
HealthCare
Office
Infrastructure
Education
Retail
BFSI
Hotels
Manufacturing
Model HPMAX-FM-10K-31

Reset default

Specification

Output Specification
Output Capacity (KVA )
10 KVA
Output Capacity (KW )
9 KW
Output Power Factor
0.9 Power Factor
Output Phase
1 Phase
Output Voltage
230 Volt
Efficiency at Full Load
> 94 %
Output Voltage Distortion
< 2 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Load Crest Factor
3:1
Output Voltage THD
< 3 %
Transfer Time
< ms
Output Waveform type
Sine Wave
Output Connections
Hard Wire 3 wire (1PH+N+G)
UPS Parallel Upto
4 Nos.
Input Specification
Input voltage range for main operations
340 - 480 Volt
Input Voltage
400 Volt
Input Phase
3 Phase
Input frequency
50/60Hz +/- 3 Hz
Input Voltage Range (Output Derated)
190 - 478 Volt
Input frequency Range
50 - 60 Hz
Input Power Factor
> 0.99
Input Connections
Hard Wire 5-wire (3PH + N + G)
Batteries & Runtime
Battery DC Bus
288 VDC
Maximum Charger Capacity
10 Amp.
Approved Battery Capacity (AH)
17 - 100 Amp.
Battery Position Option
External
Battery Type Compatibility
SMF Battery
Communication & Management
Control panel
LCD Display
SNMP Management
Optional
Physical
Maximum Height
985 Mm
Maximum Width
352 Mm
Maximum Depth
690 Mm
Net Weight
120 Kg
Environmental
Operating Temperature
0 - 40 °C
Operating Relative Humidity
5 - 95 % Rh
Other Specifications
Technology
Double Conversion Online

Documentation

Item Catalogue
Numeric-MAX-FM-1kVA-F_1
pdf

Options