KEOR MP

Keor MP UPS is a three-phase uninterruptible power supply On-line Double Conversion with 3-Level IGBT technology, PWM high frequency and with the possibility to be connected in parallel to have N+X redundancy up to total 6 units.

Designed to drive the future with innovation, the Keor MP is a groundbreaking advancement in the power backup technology. This 3-phase online double conversion monolithic UPS, featuring a module-based architecture with Three Level IGBT based Inverter technology delivers unparalleled eff icency of up to 96% in a compact design

FEATURES

  • 60-200kVA Capacity
  • PF 1 (kVA=kW)
  • 3 Phase Input / 3 Phase Output
  • 3 level IGBT- Inverter
  • High Efficiency
  • LCD/Touch Screen Display
  • Digital Signal Processor (DSP)
  • Input Power Factor Correction (PFC)
  • Parallel Capability up to 6 Units 2N & N+1 Redundancy
  • 2N Sychro
  • Smart Battery Charge Cycle
  • Genset operation compliant
  • Optimized Ventilation Against Wall installation
  • Front access operation and service
  • Full IT Connectivity
  • Wide offer of optional features and accessories
  • Model Keor MP-100KVA

    Reset default

    Specification

    Output Specification
    Output Capacity (KVA )
    100 KVA
    Output Capacity (KW )
    100 KW
    Output Power Factor
    1 Power Factor
    Output Phase
    3 Phase
    Output Voltage
    400 Volt
    Other Output Voltage
    380 Or 415 Volt
    Efficiency at Full Load
    > 96 %
    Load Crest Factor
    3:1
    Output Voltage THD
    < 3% linear load and <5% non-linear load
    Output Waveform type
    Sine Wave
    Output Connections
    Hard Wire 5-wire (3PH + N + G)
    Overload Capacity
    Yes
    UPS Parallel Upto
    6 Nos.
    Input Specification
    Input Voltage
    400 Volt
    Other Input Voltage
    380 Or 415 Volt
    Input Phase
    3 Phase
    Input frequency Range
    45 - 55 Hz
    Input Voltage Range (Output Derated)
    242 - 460 Volt
    Input voltage range for main operations
    340 - 460 Volt
    Input Power Factor
    0.99
    Input Connections
    Hard Wire 5-wire (3PH + N + G)
    Batteries & Runtime
    Battery DC Bus
    432 600 VDC
    Battery Type Compatibility
    SMF Battery
    Battery Circuit Breaker
    Inclusive
    Approved Battery Capacity (AH)
    100 - 200 Amp.
    Maximum Charger Capacity
    30 Amp.
    Communication & Management
    Control panel
    Touch Screen LCD User Interface
    SNMP Management
    Optional
    Power Management Software
    Optional
    Interface Port(s)
    RS-232, USB
    Audible noise at 1 meter from surface of unit
    < 60 Decibal
    Physical
    Maximum Height
    1200 Mm
    Maximum Width
    442 Mm
    Maximum Depth
    800 Mm
    Net Weight
    160 Kg
    Environmental
    Operating Temperature
    0 - 40 °C
    Operating Relative Humidity
    0 - 95 %
    Other Specifications
    Technology
    Double Conversion Online