Contact Us

Brand Vertiv UPS System On Line UPS Liebert Make 1 KVA 1:1 Phase On-Line UPS ( GXT MT+ CX LB Model )

Liebert Make 1 KVA 1:1 Phase On-Line UPS ( GXT MT+ CX LB Model )

UPS System On Line UPS

Price: 18762

You save 19116

Liebert® GXT MT+ CXTM is a sleek, high frequency,
double-conversion UPS with wide input voltage/
frequency and better output voltage regulation, which
makes it an ideal choice for harsh environments,
especially those facing concerns related to unstable
mains output and high load impact. This advanced
UPS provides higher availability while offering
intelligent monitoring and network management
functions.
Model GXT MT+ CX 1K LB

Reset default

Specification

Output Specification
Output Capacity (KVA )
1 KVA
Output Capacity (KW )
0.8 KW
Output Power Factor
0.8 Power Factor
Output Phase
1 Phase
Output Voltage
230 Volt
Efficiency at Full Load
> 88 %
Output Waveform type
Sine Wave
UPS Parallel Upto
Not Available
Input Specification
Input Voltage
230 Volt
Other Input Voltage
220 Or 240 Volt
Input Phase
1 Phase
Input Voltage Range (Output Derated)
110 - 280 Volt
Input voltage range for main operations
165 - 183 Volt
Input frequency Range
60 - 70 Hz
Batteries & Runtime
Battery DC Bus
36 - VDC
Maximum Charger Capacity
6 Amp.
Battery Position Option
External
Battery Type Compatibility
SMF Battery
Approved Battery Capacity (AH)
17 - 100 Amp.
Communication & Management
Control panel
LCD Display
SNMP Management
Optional
Power Management Software
In-Built
Interface Port(s)
RS-232, USB
Audible noise at 1 meter from surface of unit
< 50 Decibal
Physical
Maximum Height
220 Mm
Maximum Width
145 Mm
Maximum Depth
282 Mm
Net Weight
4.1 Kg
Environmental
Operating Temperature
0 - 40 °C
Operating Relative Humidity
5 - 95 % Rh
Other Specifications
Technology
Double Conversion Online

Features

GXT MT+ CX 1-3 KVA Features
General Features
IGBT Based Rectifier
True Online Double Conversion with DSP Control Technology for High Performance and Reliability
New Graphical LCD Display Provides UPS Data, Alarms and Helps in faults diagnostics and trouble shooting
Double Conversion Efficiency upto 90%
Active Input Power Factor Correction 0.99
0.8 Output Power Factor
Wide Input Voltage window (110 - 280 Vac) for Indian Environmental Condition and for Optimized Battery Performance
Configurable Output Voltage (200/208/220/230/240 Vac.)
Generator Compatible with Wide Input Frequency Range (40 Hz-70 Hz)
4 Stage Extendable Charging Design for optimized Battery Performance
Adjustable Battery Charging Current 1/2/4/6 Amps according to Battery Capacity and Rating
50/60 Hz Automatic Frequency Converter Mode
Intelligent Monitoring with Standard RS232/USB Port Plus Slot Available for RS485/Dry Contact/SNMP Card
Inbuilt OVCD

Documentation

Item Catalogue
GXT MT+ CX 1K LB catalouge
pdf

Options