Contact Us

Brand BPE UPS System Industrial UPS BPE Make 200 KVA 3:3 Phase Industrial On-Line UPS With Isolation Transformer

BPE Make 200 KVA 3:3 Phase Industrial On-Line UPS With Isolation Transformer

UPS System Industrial UPS

Price: 1334580

You save 1433228

Model GTX33200L50

Reset default

Specification

Output Specification
Output Capacity (KVA )
200 KVA
Output Capacity (KW )
180 KW
Output Power Factor
0.99 Power Factor
Output Phase
3 Phase
Other Output Phase
Or Phase
Output Voltage
400 Volt
Other Output Voltage
380 Or 415 Volt
Efficiency at Full Load
>95.5 %
Output Voltage Distortion
<3 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Output Frequency (not synced)
60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
Load Crest Factor
3:1
Output Voltage THD
< 3% linear load and <5% non-linear load
Transfer Time
<0 ms
Output Waveform type
Sine Wave
Output Connections
Hard Wire 5-wire (3PH + N + G)
Bypass
Built-in Static Bypass
Overload Capacity
150% for 1 minute 125% for 10 minutes
UPS Parallel Upto
Optional
Input Specification
Input Voltage
400 Volt
Other Input Voltage
380 - 415 Volt
Input Phase
3 Phase
Other Input Phase
- Phase
Input frequency
50 Or 60 Hz
Input frequency Range
40 - 70 Hz
Input Voltage Range (Output Derated)
150 - 342 Volt
Input voltage range for main operations
342 - 477 Volt
Input Power Factor
>0.99 Power Factor
Input Connections
Hard Wire 5-wire (3PH + N + G)
Input Protection
Fuse
Input Voltage THD
<3 %
Input Short Circuit Current (Maximum)
kAmps.
Input Current (Maximum)
Amp.
Batteries & Runtime
Internal Battery Capacity (VAH)
Battery Position Option
External
Battery Circuit Breaker
Approved Battery Capacity (AH)
200 - 1000 Amp.
Battery DC Bus
600 VDC
Battery Type Compatibility
Sealed Maintenance Free (SMF) / Valve Regulated Lead Acid (VRLA) type, Flooded / tubular / vented type
Communication & Management
Control panel
Touch Screen LCD User Interface
SNMP Management
Optional
Power Management Software
In-Built
Interface Port(s)
E3M_ColdStart, E3M_parallel, E3S_TempSensor
Audible Alarm
Audible and visible alarms prioritized by severity
Audible noise at 1 meter from surface of unit
Decibal
Physical
Maximum Height
1700 Mm
Maximum Width
800 Mm
Maximum Depth
860 Mm
Shipping Height
Mm
Shipping Width
Mm
Shipping Depth
Mm
Net Weight
830 Kg
Shipping weight
Kg
Colour
Black
Environmental
Operating Temperature
0 - 40 °C
Operating Relative Humidity
0 - 95 %
Operating Elevation
- Meters
Storage Temperature
-25 - 55 °C
Storage Relative Humidity
0 - 95 %
Storage Elevation
- Meters
Online thermal dissipation
Btu/Hr
Protection Class
IP20
Compliances
Compliance
BIS
Approvals
CE, EAC, IEC 62040-1-1, IEC 62040-2, IEC 62040-3, IEC 62040-4, ISTA 2B, RCM, WEEE
Other Environmental Compliance
Compliant
Other Specifications
Technology
Double Conversion Online
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Surge Protection
Yes

Documentation

Item Catalogue
BPE GTX Industrial UPS Catalogue
pdf

Options